| PROPERTIES | TEST METHOD | VALUES | TEST METHOD | VALUES |
| FPS UNITS | METRIC UNITS | |||
| SPECIFIC GRAVITY | DIN 53508 | 1.60 ± 0.05 | ASTM D297 | 1.60 ± 0.05 |
| HARDNESS | DIN 53505 | 70 ± 5 Sh A | ASTM D2240 | 70 ± 5 Sh A |
| TENSILE STRENGTH ( min ) | DIN 53504 | 994 PSI | ASTM D412 | 70 kg/cm2 |
| ELONGATION AT BREAK ( min ) | DIN 53504 | 300% | ASTM D412 | 300% |
| COMPRESSION SET (70ºC/24 hrs/25% set) (max) | DIN 53517 | 40% | ASTM D395 METHOD B | 40% |
| TEAR RESISTANCE (Angular) min | DIN 53515 | 335 Lbs/Inch | ASTM D624 | 30 Kg/cm |
| CHANGE IN PROPERTIES | ||||
| HEAT AGEING (72 hrs. AT 70ºC ) | ASTM D573 | |||
| — HARDNESS (Pts) | + 5 (Max) | + 5 (Max) | ||
| — TENSILE STRENGTH (%) | + 15 / -15 | + 15 / -15 | ||
| — ELONGATION AT BREAK (%) | – 40 | – 40 | ||
| POLYMER | 100 % NEOPRENE | 100 % NEOPRENE | ||
| OZONE RESISTANCE 100 PPHM 72 H 40ºC 30 % Strain | NO CRACKS | ASTM D 1149 | NO CRACKS | |
| CHANGE IN VOLUME (ASTM oil No.3/70 ºC/70 hrs) (%)(MAX))) | ASTM D471 | 45% | ||
| DI-ELECTRIC STRENGTH OF INSULATING MATERIALS (Kv/mm) (MIN) | CEI EN 60243-2 | 10 | ||
| TEST FOR SURFACE FLAMMABILITY, REACTION TO FIRE TESTS – SPREAD OF FLAME | IMO FTP CODE PART-5/ ISO 565-2:2006 | |||
| –CRITICAL FLUX AT EXTINGUISHMENT (CFE), Kw/m2 ( ≥7.0) | PASS | |||
| –HEAT FOR SUITABLE BURNING (Qsb), MJ/m2 (≥0.25) | PASS | |||
| –TOTAL HEAT RELEASED (Qt), MJ (≥2.0) | PASS | |||
| –PEAK HEAT RELEASE RATE (Qp), kW (≥ 10.0) | PASS | |||
| TEMPERATURE RANGE | -30º to + 100ºC | -30º to + 100ºC | ||
| COLOUR | GREY | GREY |
INTRODUCTION Determination of compliance of IMO rubber sheet as per International Maritime Organization (IMO) Fire Test Procedures (FTP) Code Part 5.
TEST METHODS & REFERENCES IMO FTP CODE Part 5; Test for surface flammability (Test for surface materials and primary deck coverings) ISO 5658-2:2006, Reaction to fire tests – Spread of Flame – Part 2: Lateral spread on building and transport products in vertical configuration.
DATE OF TEST: Fire Test Date: 14.08.2023
SPECIMEN DETAIL
| Specimen Detail (Declared by Test Sponsor) | |
| Product Type | Floor covering |
| Product Name | IMO rubber sheet ( NE 70160 grey FR IMO) |
| Density | Not declared by test sponsor |
| Mass Per Unit Area | Not declared by test sponsor |
| Specimen Size | 155X800 mm: 6 Pieces |
| Thickness | 5.13 mm |
| Color | Grey |
| Organic Content | Not declare by test sponsor |
| Number of Coating | Not declared by test sponsor |
| Orientation tested | Lengthwise |
| Exposed Face | Both faces were symmetrical, one face was exposed to fire |
| Substrate Used | Calcium silicate board |
SPECIMEN CONSTRUCTION
Specimen preparation was done by test sponsor. Preparation procedure was not shared with the laboratory.
PRE-TEST PROCEDURE
Verification of the Test Specimen
Ignito Labs was not involved in the selection of the specimen. Test specimen was supplied by the sponsor of test.
Conditioning
The specimens were stored at a temperature of 23±20C and relative humidity of 50±5% till constant mass.
FIRE TEST PROCEDURE
IMO FTP CODE PART 5
1 specimen of size 800mm in length, 155mm in width and 5.13mm in thickness has been placed at an angle of 150 from the radiant heat panel system which is set at an irradiance defined in Table 1 of Appendix 2 of IMO FTP code Part 5. Test chronometer is started once the sample is placed in testing position. Flame spread profile and other relevant parameters are monitored and recorded. Test for 2 more specimens performed in same manner and results were recorded.
OBSERVATIONS
Pre -Test Observations
The specimen was found satisfactory and fit to be tested.
Test Observations
IMO FTP CODE PART 5
| Number of specimens tested | 3 |
| Gas used in Pilot Flame | Propane |
| Distance, in mm | Time to cross reference mark, in seconds | Heat for Sustained Burning, in MJ/m2 | ||||
| S1 | S2 | S3 | S1 | S2 | S3 | |
| 50 | 21 | 19 | 23 | – | – | – |
| 100 | 30 | 32 | 30 | – | – | – |
| 150 | 36 | 38 | 35 | 1.7 | 1.8 | 1.7 |
| 200 | 57 | 55 | 50 | 2.5 | 2.4 | 2.2 |
| 250 | 83 | 86 | 80 | 3.1 | 3.2 | 3.0 |
| 300 | 132 | 134 | 136 | 4.0 | 4.1 | 4.1 |
| 350 | 280 | 275 | 270 | 6.6 | 6.5 | 6.4 |
| 400 | 425 | 415 | 420 | 9.1 | 8.5 | 9.0 |
| 450 | ||||||
| 500 | ||||||
| 550 | ||||||
| 600 | ||||||
| 650 | ||||||
| 700 | ||||||
| 750 | ||||||
| Parameter | Test Specimen | Average | ||
| S1 | S2 | S3 | ||
| Mass of Specimen, in g | 1020 | 1015 | 1022 | 1019 |
| Time to Ignition, in seconds | 6 | 5 | 7 | 6.00 |
| Time to Extinguishment, in seconds | 425 | 415 | 420 | 420.0 |
| Distance of Extinguishment, in mm | 370 | 380 | 370 | 370.0 |
| Critical Flux at Extinguishment (CFE), in kW/m2 | 21.5 | 20.4 | 21.5 | 21.1 |
| Heat for Ignition (Qig), in MJ/m2 | 1.7 | 1.8 | 1.7 | 1.7 |
| Average Heat for Sustained Burning (Qsb), in MJ/m2 | 6.6 | 6.5 | 6.4 | 6.5 |
| Total Heat Released (Qt), in MJ | 0.61 | 0.54 | 0.41 | 0.52 |
| Peak Heat Release Rate (Qp), in kW | 3.32 | 2.94 | 3.14 | 3.13 |
| Burning Droplets (Yes/No) | No | No | No | – |
| Flashing, unstable flame front, sparks, glowing, charring, melting, flaming drips, disintegration of
the specimen, fissures, fusion, changes in form |
– |
– |
– |
– |
| Test Duration, in minute | 20 | 20 | 20 | – |
SUMMARY OF RESULTS
Test specimen has been tested and evaluated in accordance with IMO FTP code Part 5. The results are given below.
IMO FTP CODE PART 5
| Other Relevant Parameters | Observations |
| Critical Flux at Extinguished (CFE), in kW/m2 | 21.1 |
| Average Heat for Sustained Burning (Qsb), in MJ/m2 | 6.5 |
| Total Heat Released (Qt), in MJ | 0.52 |
| Peak Heat Release Rate (Qp), in kW | 3.13 |
| Did specimens meet the Bulkhead, wall and ceiling Lining criteria? (Yes/No) | Yes |
| Did specimens meet the floor covering criteria? (Yes/No) | Yes |
| Did specimens meet the Primary Deck covering criteria? (Yes/No) | Yes |
CLASSFICIATION CRITERIA
IMO FTP CODE PART 5
Materials having average values for all the surface flammability criteria that comply with the values as listed in table 1, are considered to meet the requirement for low flame-spread in compliance with the relevant regulations in chapter II-2 of the Convention.
| Class | Bulkhead, wall, and ceiling linings | Floor coverings | Primary deck coverings |
| CFE (kW/m2) | ≥ 20.0 | ≥ 7.0 | ≥ 7.0 |
| Qsb (MJ/m2) | ≥ 1.5 | ≥ 0.25 | ≥ 0.25 |
| Qt (MJ) | ≤ 0.7 | ≤ 2.0 | ≤ 2.0 |
| Qp (kW) | ≤ 4.0 | ≤ 10.0 | ≤ 10.0 |
| Burning droplets | Not produced | No more than 10 burning drops | Not produced |
Where:
CFE = Critical flux at extinguishment
Qsb = Heat for sustained burning
Qt = Total heat release
Qp = Peak heat release rate
PHOTOS

Sample Before Test Sample After Test